关键词:
局部放电
射频信号
放电量
高电压技术
摘要:
The converter transformer is one of the most critical equipments in high-voltage direct current transmission ***-side windings have to withstand complex stresses combined of AC,DC,and pulsed *** discharges(PDs) can thus easily occur in oil-impregnated paper *** current paper presents the statistical phase-resolved distributions of partial discharges in oil-paper insulation under combined AC and DC voltage ***,the voltages in the converter transformer were *** the experiments,four artificial insulation defect models were designed to generate PD signals under AC-DC combined voltage stress detected by a Rogowski coil *** including the φ-q-n data of these PD signals were *** variations of φ-q-n data generated by PDs in different insulation defect models were analyzed while increasing the test *** results showed that the PD phase-resolved distributions of different insulation defect models were different from one *** findings of the current study are useful in further research on the mechanism and pattern recognition of PDs in converter transformers.